# Duct design for Lot 308, approaches B and C

Duct design following the ACCA Manual D procedure. Representative equipment, not a selected model. This software is not ACCA-approved. First-pass design for review by a qualified designer.

Produced by ducts.py in this folder from loads-v1/results.csv (room loads), the loads engine's hourly room loads (for the zone peaks), rooms.csv (extents) and the two research notes in research/ducts/. Every number below is computed there. Imperial units. Rulings applied: test-plans/schedule-first/ducts-v1/decisions.md.

## 1. Design basis and equipment assumed

Loads: heating 29,843 Btuh; cooling sensible block 28,993 Btuh at hour 16; sum of room peaks 31,585; latent 800; total cooling 29,793 Btuh (2.48 tons). Altitude factor 0.903, sensible factor 0.975 Btuh per cfm per F, reference delta T 20 F, so 19.50 Btuh per cfm and a block cfm of 1,486 at that delta T; the design delta T per approach is in section 2.

Zone loads from the engine's hourly room loads: main floor peaks at hour 17 with 15,710 Btuh (805 cfm); upper floor at hour 15 with 13,587 Btuh (697 cfm). Sum of zone peaks 1,502 cfm against the block 1,486 cfm.

### Approach B: one variable-speed heat pump, zoned by floor, two secondary trunks, no bypass

Representative equipment: Goodman AVPTC37C14 multi-position variable-speed air handler (3 ton chassis, internal coil) with a 3 ton inverter heat pump. Status: assumed (representative of the class, not a selection).

Blower: high-stage target 1,200 cfm at the 3 ton setting, default low stage 804 cfm, chassis maximum 1,315 cfm (SS-GAVPTC airflow data, https://canadahvac.com/wp-content/uploads/2023/01/GOLD_SILVER-FURNACE-AVPTC.pdf; the 1,315 cfm figure from a distributor listing). 400 cfm per ton. AVPTC airflow targets are constant-cfm ECM targets; SS-GAVPTC note 3 caps the recommended external static at 0.50 in wc.

Zoning: two-zone panel, no bypass, 15 percent bleed to the idle zone, blower follows the calling zone (Manual Zr).

### Approach C: two ducted mini-split heads, one per floor

Representative equipment: Mitsubishi PEAD-A18AA8 (main floor) and PEAD-A15AA8 (upper floor) mid-static ceiling-concealed ducted heads. Status: assumed (representative of the class, not a selection).

- main floor: PEAD-A18AA8, 18,000 Btuh cooling / 19,000 heating nominal, airflow 424 / 512 / 600 cfm low / mid / high (dry coil), 540 cfm high with a wet coil, external static selectable 0.14/0.20/0.28/0.40/0.60 in wc, design at 0.40 (Mitsubishi service manual HWE2109A, https://www.mitsubishitechinfo.ca/sites/default/files/SH_PEAD-A09_36AA8_HWE2109A.pdf).

- upper floor: PEAD-A15AA8, 15,000 Btuh cooling / 18,000 heating nominal, airflow 424 / 512 / 600 cfm low / mid / high (dry coil), 540 cfm high with a wet coil, external static selectable 0.14/0.20/0.28/0.40/0.60 in wc, design at 0.40 (Mitsubishi service manual HWE2109A, https://www.mitsubishitechinfo.ca/sites/default/files/SH_PEAD-A09_36AA8_HWE2109A.pdf).

## 2. Room and zone cfm

Design delta T follows the equipment table (brief: 20 F unless the table says otherwise). B: one blower at 1,200 cfm carries the 28,993 Btuh block, so delta T = 24.8 F. C: each head's wet-coil high airflow (540 cfm) carries its zone, so delta T = 29.8 F main and 25.8 F upper. The 20 F column is the load-only figure for comparison.

| Room | Name | sf | Heat Btuh | Cool peak Btuh | Hour | Cool at house hour | cfm at 20 F | B cfm own peak | B cfm block share | C cfm own peak | cfm heating at 30 F rise | Outlets |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1 | Entry / Stair Hall (incl. under-st | 186 | 3,732 | 2,797 | 15 | 2,743 | 143 | 116 | 114 | 96 | 128 | M1a, M1b |
| M2 | Powder | 37 | 816 | 317 | 17 | 312 | 16 | 13 | 13 | 11 | 28 | none (door undercut; load carried by M1a) |
| M3 | Broom Closet | 17 | 382 | 149 | 17 | 146 | 8 | 6 | 6 | 5 | 13 | none (door undercut; load carried by M1a) |
| M4 | Living Room | 327 | 4,103 | 4,788 | 16 | 4,788 | 245 | 198 | 198 | 165 | 140 | M4A, M4B |
| M5 | Dining Room | 257 | 5,953 | 6,116 | 17 | 5,420 | 314 | 253 | 224 | 210 | 203 | M5W, M5E |
| M6 | Kitchen (incl. pantry and refriger | 304 | 2,662 | 2,586 | 8 | 2,221 | 133 | 107 | 92 | 89 | 91 | M6 |
| U1 | Loft (incl. open stairwell footpri | 238 | 2,360 | 3,583 | 16 | 3,583 | 184 | 148 | 148 | 142 | 81 | U1a, U1b |
| U2 | Master Bedroom | 224 | 2,209 | 3,083 | 18 | 2,831 | 158 | 128 | 117 | 123 | 76 | U2 |
| U3 | Master W.I.C. | 91 | 1,103 | 1,119 | 8 | 842 | 57 | 46 | 35 | 44 | 38 | U3 |
| U4 | Master Bath (incl. toilet room, li | 183 | 1,044 | 1,346 | 8 | 884 | 69 | 56 | 37 | 53 | 36 | U4 |
| U5 | Laundry | 74 | 151 | 152 | 14 | 142 | 8 | 6 | 6 | 6 | 5 | none (door undercut; load carried by U1a) |
| U6 | Upper Hall + Linen | 44 | 123 | 113 | 14 | 107 | 6 | 5 | 4 | 4 | 4 | none (door undercut; load carried by U1a) |
| U7 | Bedroom #3 (incl. closet) | 208 | 2,446 | 2,391 | 13 | 2,070 | 123 | 99 | 86 | 95 | 84 | U7 |
| U8 | Bath (hall) | 59 | 164 | 151 | 14 | 142 | 8 | 6 | 6 | 6 | 6 | none (door undercut; load carried by U1a) |
| U9 | Bedroom #2 | 158 | 1,746 | 2,118 | 15 | 2,109 | 109 | 88 | 87 | 84 | 60 | U9 |
| U10 | W.I.C. (Bedroom #2) | 49 | 849 | 776 | 11 | 654 | 40 | 32 | 27 | 31 | 29 | U10 |

Branches are sized to the own-peak column (Alan's ruling); the block-share column is what the balancer sets when every room calls at once. Rooms under 20 cfm get no outlet; their load is folded into the adjacent outlet shown.

| Zone | Rooms | Heat Btuh | Cool peak Btuh | Hour | Sum of room peaks | Zone cfm at 20 F | B zone cfm | C zone cfm |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| main | M1, M2, M3, M4, M5, M6 | 17,648 | 15,710 | 17 | 16,753 | 805 | 650 | 540 |
| upper | U1, U2, U3, U4, U5, U6, U7, U8, U9, U10 | 12,195 | 13,587 | 15 | 14,832 | 697 | 562 | 540 |
| house | block | 29,843 | 28,993 | 16 | 31,585 | 1,486 | 1,200 | 1,080 |

Zone hourly cooling on the design day (Btuh), which is what the zoning decision rests on:

| Hour | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| main | 9,784 | 10,527 | 10,846 | 11,029 | 11,563 | 12,802 | 14,016 | 14,620 | 15,629 | 15,710 | 13,811 | 8,677 | 7,592 |
| upper | 8,265 | 9,431 | 10,080 | 10,453 | 11,012 | 12,154 | 13,160 | 13,587 | 13,364 | 12,812 | 11,490 | 7,246 | 6,067 |

## 3. Static pressure budget

### Approach B

| Item | in wc | Source | Status |
| --- | --- | --- | --- |
| external static, design | 0.500 | AVPTC airflow targets are constant-cfm ECM targets; SS-GAVPTC note 3 caps the recommended external static at 0.50 in wc | sourced |
| wet coil | -0.000 | inside the AVPTC cabinet, within the external static rating (SS-GAVPTC); a separate cased coil of this class, Goodman CAPT3743C4, is 0.143 in wc wet at 1,200 cfm (SS-GCoil airflow data) and is shown for comparison only | sourced |
| media filter, 4 in MERV 11 at the air handler return | -0.110 | Aprilaire 210 (20x25x4) 0.11 in wc at 1,200 cfm, Aprilaire replacement media table | sourced |
| supply register | -0.031 | Hart & Cooley A618 engineering data: pressure loss 0.031 in wc at 700 fpm face velocity; Manual D default 0.03 (MD3 copy, section 6-5) | sourced |
| return grille | -0.030 | Manual D default when OEM data is missing (MD3 copy, section 6-5) | licensed-unverified |
| balancing damper, wide open | -0.030 | Manual D default (MD3 copy, section 6-5) | licensed-unverified |
| zone damper, wide open | -0.033 | Honeywell ARD round automatic damper submittal: 0.0329 in wc at 800 fpm, full open | sourced |
| available static pressure | 0.266 | ESP less the components | derived |

### Approach C

| Item | in wc | Source | Status |
| --- | --- | --- | --- |
| external static, design | 0.400 | PEAD service manual HWE2109A: airflow 424-512-600 cfm (low-mid-high, dry coil) at field-selected external static 0.14/0.20/0.28/0.40/0.60 in wc; the 0.40 setting is used, 0.60 costs 3 dB(A) | sourced |
| wet coil | -0.000 | inside the PEAD cabinet, within the external static rating (service manual fan performance is external static) | sourced |
| media filter, 4 in MERV 11 at the unit return | -0.040 | Aprilaire 210 initial drop 0.04 in wc at 600 cfm, Aprilaire curve as quoted on hvac-talk.com; 0.11 at 1,200 cfm is the catalog value | sourced (secondary) |
| supply register | -0.031 | Hart & Cooley A618: 0.031 in wc at 700 fpm face; Manual D default 0.03 | sourced |
| return grille | -0.030 | Manual D default (MD3 copy, section 6-5) | licensed-unverified |
| balancing damper, wide open | -0.030 | Manual D default (MD3 copy, section 6-5) | licensed-unverified |
| available static pressure | 0.269 | ESP less the components | derived |

## 4. Effective length and friction rate

### Approach B

Longest supply path: to outlet U9 (U9), 212 ft effective. Longest return path: R-master, 208 ft effective. TEL 420 ft. Friction rate worksheet value ASP x 100 / TEL = 0.266 x 100 / 420 = 0.063 in wc per 100 ft; design friction rate 0.063 (held inside the wedge 0.06 to 0.18). Sizes converged in 2 iterations.

| Side | Manual D group | Item | C | EL ft | Appendix 3 comparator |
| --- | --- | --- | --- | --- | --- |
| supply | straight | 14x20 riser |  | 4.5 |  |
| supply | straight | riser box |  | 2.0 |  |
| supply | group 1 | air handler outlet into the supply plenum | 0.14 | 8.8 |  |
| supply | group 1 | plenum box outlet into a trunk: rectangular radius elbow r/W 1.0, H/W  | 0.38 | 24.0 | MD3 copy 1L: 40 ft |
| supply | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 9.5 | MD3 copy 12: 8 ft |
| supply | straight | trunk straight to the takeoff |  | 8.0 |  |
| supply | group 2 | branch takeoff, 45 deg entry tap, rectangular trunk to round branch, V | 0.73 | 46.1 | MD3 copy 2B: 45 ft |
| supply | straight | runout span (flex) |  | 11.3 |  |
| supply | straight | wall stack |  | 8.0 |  |
| supply | group 11 | flex duct 90 deg bend at R/D 1.0 or more (treated as a smooth round el | 0.22 | 13.9 | MD3 copy 8D: 65 ft |
| supply | group 4 | boot into a wall stack (round elbow r/D 1.0, 0.33, plus round-to-recta | 1.2 | 75.7 | MD3 copy 4G: 80 ft |
| return | straight | stack |  | 8.0 |  |
| return | straight | 8 in round galvanized west in bay y31.83 to 33.83, x22 to x18.5 |  | 3.5 |  |
| return | straight | 8 in round south along x18.5 through five truss webs, y33.83 to y23.83 |  | 10.0 |  |
| return | straight | 8 in round west in bay y21.83 to 23.83, x18.5 to x11.5 |  | 7.0 |  |
| return | straight | return trunk and drop |  | 7.0 |  |
| return | group 7 | return wall stack: high-wall grille entry (0.5) plus stack head turn r | 1.6 | 61.1 |  |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 5.7 | MD3 copy 12: 8 ft |
| return | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 5.7 | MD3 copy 12: 8 ft |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 6 | branch return joining the return trunk, 45 deg entry, Qb/Qc 0.5, Vc un | 0.55 | 21.0 | MD3 copy 6H: 15 ft |
| return | group 10 | return trunk turning down into the drop, rectangular radius elbow | 0.21 | 8.0 |  |
| return | group 14 | return duct into the media filter cabinet, transition Ao/A1 0.5, 30 de | 0.15 | 5.7 |  |
| return | group 5 | return plenum into the air handler inlet, abrupt entry | 1.0 | 38.2 | MD3 copy 5I: 30 ft |

Every outlet's supply effective length: M1a 135; M1b 183; M4A 148; M4B 138; M5W 155; M5E 164; M6 147; U1a 173; U1b 198; U2 195; U3 175; U4 164; U7 199; U9 212; U10 163. Returns: R-main 94; R-upper 149; R-master 208.

### Approach C

Longest supply path: to outlet U9 (U9), 241 ft effective. Longest return path: R-master, 199 ft effective. TEL 440 ft. Friction rate worksheet value ASP x 100 / TEL = 0.269 x 100 / 440 = 0.061 in wc per 100 ft; design friction rate 0.061 (held inside the wedge 0.06 to 0.18). Sizes converged in 2 iterations.

| Side | Manual D group | Item | C | EL ft | Appendix 3 comparator |
| --- | --- | --- | --- | --- | --- |
| supply | straight | supply plenum in the laundry soffit, head outlet to the west drop |  | 5.0 |  |
| supply | straight | west drop through the laundry floor at x11.5 to 13 |  | 1.5 |  |
| supply | group 1 | air handler outlet into the supply plenum | 0.14 | 8.8 |  |
| supply | group 9 | trunk feed splitting into two legs, double 45 deg wye, Ab/Ac 0.5, Qb/Q | 0.4 | 25.2 |  |
| supply | group 8 | rectangular radius elbow, r/W 1.0, H/W 0.75, 90 deg | 0.23 | 14.5 | MD3 copy 8, four-piece: 20 ft |
| supply | group 8 | rectangular radius elbow, r/W 1.0, H/W 0.75, 90 deg | 0.23 | 14.5 | MD3 copy 8, four-piece: 20 ft |
| supply | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 9.5 | MD3 copy 12: 8 ft |
| supply | straight | trunk straight to the takeoff |  | 6.5 |  |
| supply | group 2 | branch takeoff, 45 deg entry tap, rectangular trunk to round branch, V | 0.73 | 46.1 | MD3 copy 2B: 45 ft |
| supply | straight | runout span (flex) |  | 11.3 |  |
| supply | straight | wall stack |  | 8.0 |  |
| supply | group 11 | flex duct 90 deg bend at R/D 1.0 or more (treated as a smooth round el | 0.22 | 13.9 | MD3 copy 8D: 65 ft |
| supply | group 4 | boot into a wall stack (round elbow r/D 1.0, 0.33, plus round-to-recta | 1.2 | 75.7 | MD3 copy 4G: 80 ft |
| return | straight | stack |  | 8.0 |  |
| return | straight | 8 in round west in bay y31.83 to 33.83, x22 to x18 |  | 4.0 |  |
| return | straight | 8 in round south along x18 through four truss webs, y33.83 to y25.83,  |  | 8.0 |  |
| return | straight | 8 in round west in bay y23.83 to 25.83 to x16.3, then the riser box up |  | 5.0 |  |
| return | group 7 | return wall stack: high-wall grille entry (0.5) plus stack head turn r | 1.6 | 61.1 |  |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 5.7 | MD3 copy 12: 8 ft |
| return | group 12 | trunk reduction, rectangular two-sides-parallel transition Ao/A1 0.5,  | 0.15 | 5.7 | MD3 copy 12: 8 ft |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 8 | round 5-piece elbow, r/D 1.5, 90 deg | 0.24 | 9.2 | MD3 copy 8, four-piece: 20 ft |
| return | group 6 | branch return joining the return trunk, 45 deg entry, Qb/Qc 0.5, Vc un | 0.55 | 21.0 | MD3 copy 6H: 15 ft |
| return | group 14 | return duct into the media filter cabinet, transition Ao/A1 0.5, 30 de | 0.15 | 5.7 |  |
| return | group 5 | return plenum into the air handler inlet, abrupt entry | 1.0 | 38.2 | MD3 copy 5I: 30 ft |

Every outlet's supply effective length: M1a 149; M1b 196; M4A 162; M4B 151; M5W 168; M5E 177; M6 160; U1a 202; U1b 227; U2 223; U3 202; U4 191; U7 226; U9 241; U10 191. Returns: R-main 82; R-upper 83; R-master 199.

Equivalent lengths are ASHRAE loss coefficients (public, Principles of HVAC 9th ed. supplement) converted at Manual D's normalisation, 900 fpm and 0.08 for supply, 700 fpm and 0.08 for return; every path in this house runs below 900 fpm, so the values are conservative (Butler). The Appendix 3 comparators are from the MD3 copy at genewoltz.com and are licensed and unverified; where the two differ by more than a factor of two (the wall-stack boot 4G at 80 ft against 76 ft here, the flex bend 8D at 65 ft against 14 ft here for a properly radiused bend) the drawing must specify the fitting, not the group.

## 5. Trunk and runout schedules

### Approach B, trunks

| Segment | ft | cfm | Round at FR in | Slide rule in | Rect in | De in | fpm | Friction |  | Serves |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| main-1 | 0.7 | 694 | 13.1 | 13.1 | 12x12 | 13.1 | 694 | 0.062 |  | M1a M1b M4A M4B M5W M5E M6 |
| main-2 | 8.3 | 559 | 12.1 | 12.0 | 12x12 | 13.1 | 559 | 0.042 |  | M4A M4B M5W M5E M6 |
| main-3 | 2.0 | 482 | 11.4 | 11.3 | 12x12 | 13.1 | 482 | 0.032 |  | M4A M5W M5E M6 |
| main-4 | 2.0 | 375 | 10.4 | 10.2 | 12x12 | 13.1 | 375 | 0.021 |  | M4A M5W M5E |
| main-5 | 4.5 | 254 | 9.0 | 8.8 | 12x6 | 9.1 | 508 | 0.059 | reduce | M5W M5E |
| upper_w-1 | 2.0 | 285 | 9.4 | 9.2 | 10x8 | 9.8 | 513 | 0.052 |  | U1a U1b U9 U10 |
| upper_w-2 | 1.0 | 253 | 9.0 | 8.7 | 10x8 | 9.8 | 455 | 0.042 |  | U1a U1b U9 |
| upper_w-3 | 5.5 | 88 | 6.1 | 5.7 | 6x6 | 6.6 | 352 | 0.044 | reduce | U9 |
| upper_e-1 | 6.0 | 329 | 9.9 | 9.7 | 12x8 | 10.7 | 494 | 0.044 |  | U2 U3 U4 U7 |
| upper_e-2 | 4.0 | 201 | 8.2 | 8.0 | 12x8 | 10.7 | 302 | 0.018 |  | U3 U4 U7 |
| upper_e-3 | 3.0 | 102 | 6.4 | 6.1 | 6x6 | 6.6 | 408 | 0.057 | reduce | U3 U4 |
| upper_e-4 | 2.0 | 46 | 4.8 | 4.4 | 6x6 | 6.6 | 184 | 0.014 |  | U3 |

### Approach B, runouts

| Run | Room | cfm | Material | Exact in | Slide rule in | Size | fpm | Friction | Span ft | Stack ft | Fitting EL ft | Path EL ft | A618 | Face fpm |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1a | M1+M2+M3 | 83 | flex | 6.2 | 6.3 | 7 in | 311 | 0.035 | 9.5 |  | 86 | 135 | 8x4 | 532 |
| M1b | M1 | 52 | rigid | 5.0 | 4.6 | 5 in | 381 | 0.063 | 26.5 |  | 116 | 183 | 8x4 | 333 |
| M4A | M4 | 121 | flex | 7.2 | 7.3 | 8 in | 347 | 0.036 | 10.3 |  | 86 | 148 | 12x4 | 504 |
| M4B | M4 | 77 | flex | 6.0 | 6.1 | 7 in | 288 | 0.030 | 3.8 |  | 86 | 138 | 8x4 | 494 |
| M5W | M5 | 127 | flex | 7.3 | 7.4 | 8 in | 364 | 0.040 | 3.2 |  | 86 | 155 | 12x4 | 529 |
| M5E | M5 | 127 | flex | 7.3 | 7.4 | 8 in | 364 | 0.040 | 12.2 |  | 86 | 164 | 12x4 | 529 |
| M6 | M6 | 107 | flex | 6.8 | 6.9 | 7 in | 400 | 0.056 | 10.8 |  | 86 | 147 | 10x4 | 540 |
| U1a | U1+U5+U6+U8 | 91 | flex | 6.4 | 6.5 | 7 in | 341 | 0.041 | 0.7 | 8 | 122 | 173 | 8x4 | 583 |
| U1b | U1 | 74 | flex | 6.0 | 6.0 | 6 in | 377 | 0.061 | 11.7 | 8 | 136 | 198 | 8x4 | 474 |
| U2 | U2 | 128 | flex | 7.3 | 7.4 | 8 in | 367 | 0.040 | 6.2 | 8 | 136 | 195 | 12x4 | 533 |
| U3 | U3 | 46 | flex | 5.0 | 4.9 | 5 in | 337 | 0.062 | 11.7 |  | 100 | 175 | 8x4 | 295 |
| U4 | U4 | 56 | flex | 5.4 | 5.4 | 6 in | 285 | 0.036 | 2.2 |  | 100 | 164 | 8x4 | 359 |
| U7 | U7 | 99 | flex | 6.6 | 6.7 | 7 in | 370 | 0.048 | 6.0 | 8 | 136 | 199 | 10x4 | 500 |
| U9 | U9 | 88 | flex | 6.4 | 6.4 | 7 in | 329 | 0.039 | 11.3 | 8 | 136 | 212 | 8x4 | 564 |
| U10 | U10 | 32 | rigid | 4.2 | 3.8 | 5 in | 235 | 0.027 | 20.3 |  | 101 | 163 | 8x4 | 205 |

### Approach B, returns

| Return | Serves | cfm | Duct | fpm | Friction | EL ft | Grille free sq in | Grille |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| R-main | main zone | 650 | 14x10 | 669 | 0.060 | 94 | 250 | 30x10 sidewall grille on the alcove north wall (y25.83), liv |
| R-upper | upper zone | 434 | 14x8 | 558 | 0.051 | 149 | 167 | 30x8 high wall grille, loft east wall (x9.5), y21 to 23.5, t |
| R-master | U2 | 128 | 7 in round | 479 | 0.062 | 208 | 49 | 14x8 high sidewall grille, master south wall (y33) at x22, t |

### Approach C, trunks

| Segment | ft | cfm | Round at FR in | Slide rule in | Rect in | De in | fpm | Friction |  | Serves |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| main-1 | 0.7 | 575 | 12.3 | 12.2 | 14x10 | 12.9 | 591 | 0.048 |  | M1a M1b M4A M4B M5W M5E M6 |
| main-2 | 8.3 | 463 | 11.3 | 11.2 | 14x10 | 12.9 | 476 | 0.033 |  | M4A M4B M5W M5E M6 |
| main-3 | 2.0 | 399 | 10.7 | 10.6 | 14x10 | 12.9 | 410 | 0.025 |  | M4A M5W M5E M6 |
| main-4 | 2.0 | 310 | 9.8 | 9.5 | 14x10 | 12.9 | 319 | 0.016 |  | M4A M5W M5E |
| main-5 | 4.5 | 210 | 8.4 | 8.2 | 8x8 | 8.7 | 472 | 0.052 | reduce | M5W M5E |
| upper_w-1 | 0.5 | 274 | 9.3 | 9.1 | 10x8 | 9.8 | 493 | 0.049 |  | U1a U1b U9 U10 |
| upper_w-2 | 1.0 | 243 | 8.9 | 8.7 | 10x8 | 9.8 | 437 | 0.039 |  | U1a U1b U9 |
| upper_w-3 | 5.5 | 84 | 6.0 | 5.7 | 6x6 | 6.6 | 336 | 0.040 | reduce | U9 |
| upper_e-1 | 4.0 | 315 | 9.8 | 9.6 | 12x8 | 10.7 | 472 | 0.041 |  | U2 U3 U4 U7 |
| upper_e-2 | 4.0 | 192 | 8.2 | 7.9 | 12x8 | 10.7 | 288 | 0.017 |  | U3 U4 U7 |
| upper_e-3 | 3.0 | 97 | 6.3 | 6.0 | 6x6 | 6.6 | 388 | 0.052 | reduce | U3 U4 |
| upper_e-4 | 2.0 | 44 | 4.7 | 4.4 | 6x6 | 6.6 | 176 | 0.013 |  | U3 |

### Approach C, runouts

| Run | Room | cfm | Material | Exact in | Slide rule in | Size | fpm | Friction | Span ft | Stack ft | Fitting EL ft | Path EL ft | A618 | Face fpm |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1a | M1+M2+M3 | 69 | flex | 5.8 | 5.9 | 6 in | 351 | 0.053 | 9.5 |  | 86 | 149 | 8x4 | 442 |
| M1b | M1 | 43 | rigid | 4.7 | 4.3 | 5 in | 315 | 0.045 | 26.5 |  | 116 | 196 | 8x4 | 276 |
| M4A | M4 | 100 | flex | 6.7 | 6.8 | 7 in | 374 | 0.049 | 10.3 |  | 86 | 162 | 10x4 | 505 |
| M4B | M4 | 64 | flex | 5.7 | 5.7 | 6 in | 326 | 0.046 | 3.8 |  | 86 | 151 | 8x4 | 410 |
| M5W | M5 | 105 | flex | 6.8 | 6.9 | 7 in | 393 | 0.054 | 3.2 |  | 86 | 168 | 10x4 | 530 |
| M5E | M5 | 105 | flex | 6.8 | 6.9 | 7 in | 393 | 0.054 | 12.2 |  | 86 | 177 | 10x4 | 530 |
| M6 | M6 | 89 | flex | 6.4 | 6.5 | 7 in | 333 | 0.040 | 10.8 |  | 86 | 160 | 8x4 | 571 |
| U1a | U1+U5+U6+U8 | 88 | flex | 6.4 | 6.5 | 7 in | 329 | 0.039 | 0.7 | 8 | 122 | 202 | 8x4 | 564 |
| U1b | U1 | 71 | flex | 5.9 | 5.9 | 6 in | 362 | 0.056 | 11.7 | 8 | 136 | 227 | 8x4 | 455 |
| U2 | U2 | 123 | flex | 7.3 | 7.4 | 8 in | 352 | 0.037 | 6.2 | 8 | 136 | 223 | 12x4 | 512 |
| U3 | U3 | 44 | flex | 4.9 | 4.9 | 5 in | 323 | 0.057 | 11.7 |  | 100 | 202 | 8x4 | 282 |
| U4 | U4 | 53 | flex | 5.3 | 5.3 | 6 in | 270 | 0.032 | 2.2 |  | 100 | 191 | 8x4 | 340 |
| U7 | U7 | 95 | flex | 6.6 | 6.7 | 7 in | 355 | 0.045 | 6.0 | 8 | 136 | 226 | 10x4 | 480 |
| U9 | U9 | 84 | flex | 6.3 | 6.3 | 7 in | 314 | 0.035 | 11.3 | 8 | 136 | 241 | 8x4 | 538 |
| U10 | U10 | 31 | rigid | 4.2 | 3.8 | 5 in | 227 | 0.025 | 20.3 |  | 101 | 191 | 8x4 | 199 |

### Approach C, returns

| Return | Serves | cfm | Duct | fpm | Friction | EL ft | Grille free sq in | Grille |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| R-main | main zone | 540 | 16x8 | 608 | 0.057 | 82 | 207 | 30x10 sidewall grille on the alcove north wall (y25.83), kit |
| R-upper | upper zone | 417 | 10x10 | 600 | 0.060 | 83 | 160 | 30x10 wall grille through the loft east wall (x9.5) at y23.5 |
| R-master | U2 | 123 | 7 in round | 460 | 0.058 | 199 | 47 | 14x8 high sidewall grille, master south wall (y33) at x22, t |

## 6. Outlet and return schedule

| Outlet | Room | Type | (x, y) ft | cfm | Register | Face fpm | Ps in wc | T75 ft design | T75 ft low stage | Note |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1a | M1 | ceiling | (7.0, 31.0) | 83 | 8x4 | 532 | 0.018 | n/a | n/a | hall ceiling, 2-way, blowing south; placement report put the M1 outlet at x4,y12 |
| M1b | M1 | ceiling | (4.0, 12.0) | 52 | 8x4 | 333 | 0.007 | n/a | n/a | entry ceiling at x4,y12 (placement report); round galvanized west in bay y27.83  |
| M4A | M4 | ceiling | (4.0, 40.5) | 121 | 12x4 | 504 | 0.016 | n/a | n/a | under the loft, long throw north along the west glass; y40.5 not y38 so the flex |
| M4B | M4 | ceiling | (11.0, 36.0) | 77 | 8x4 | 494 | 0.016 | n/a | n/a | toward the island end |
| M5W | M5 | ceiling | (16.5, 45.5) | 127 | 12x4 | 529 | 0.018 | n/a | n/a | in the 3 ft inside ceiling strip y43.83 to 47, throwing north |
| M5E | M5 | ceiling | (26.0, 45.0) | 127 | 12x4 | 529 | 0.018 | n/a | n/a | east in bay y43.83 to 45.83, throwing north |
| M6 | M6 | ceiling | (24.0, 38.0) | 107 | 10x4 | 540 | 0.018 | n/a | n/a | 2-way east and north, away from the hood at x31,y31 |
| U1a | U1 | sidewall | (9.5, 27.0) | 91 | 8x4 | 583 | 0.021 | n/a | n/a | loft east wall (laundry partition), 8 ft high, blowing west |
| U1b | U1 | sidewall | (9.5, 38.0) | 74 | 8x4 | 474 | 0.014 | n/a | n/a | loft east wall (master partition), 8 ft high, blowing west; flex north through t |
| U2 | U2 | sidewall | (21.0, 33.0) | 128 | 12x4 | 533 | 0.018 | n/a | n/a | south wall (master bath partition), 8 ft high, blowing north 14 ft; x21 keeps cl |
| U3 | U3 | floor | (30.0, 38.0) | 46 | 8x4 | 295 | 0.006 | n/a | n/a | 4x10 floor register near the east transom; y38 keeps the flex under 15 ft |
| U4 | U4 | floor | (28.0, 29.0) | 56 | 8x4 | 359 | 0.008 | n/a | n/a | 4x10 floor register outside the wet zone, over the kitchen |
| U7 | U7 | sidewall | (25.0, 20.83) | 99 | 10x4 | 500 | 0.016 | n/a | n/a | north wall (bath partition), blowing south 15 ft; the last bays are over the gar |
| U9 | U9 | sidewall | (3.5, 17.0) | 88 | 8x4 | 564 | 0.020 | n/a | n/a | north wall (loft partition), blowing south; over the entry, inside |
| U10 | U10 | floor | (11.0, 6.5) | 32 | 8x4 | 205 | 0.003 | n/a | n/a | 4x10 floor register; round galvanized south through the truss webs over the gara |

Outlet locations follow research/ducts/placement-and-comfort-fable.md section 4 except where noted (M1 split into hall and entry, M4A moved 2.5 ft north, U3 moved 2 ft south, U2 4 ft east, U10 2 ft east) to keep flex spans under 15 ft and runs clear of each other. Register data: Hart & Cooley A618 double-deflection engineering sheet, https://hartandcooley.com/uploads/a618_621.pdf (Ak, pressure loss by face velocity, throw to 75 fpm for 10x6 and 12x6). The same outlets serve both approaches.

Returns and transfer grilles are in the layout files. Both approaches: one filter grille per floor plus a dedicated master-suite return; transfer grilles over the bedroom 2 and 3 doors. The cfm column is approach B's; C's outlet cfm are in section 5 (same registers, one size smaller in three places).

## 6b. Balancing at part load

Both approaches balance each zone to its own season. Cooling: dampers set at the design-day zone peak hour (main hour 17, upper hour 15) to the own-peak column, then trimmed to the block-share column so the sum matches the blower; the east rooms (M6, U3, U4) will run 10 to 30 percent short at 8 AM and the master (U2) 20 percent short at 6 PM, which is the diversity the loads report already quantified and which a fixed damper cannot remove. Heating: the same dampers are left alone and the heating fan speed does the work; the heating cfm at a 30 F rise is about 0.78 of the cooling cfm on average, and rooms whose heating share is high relative to cooling (M1 entry, U7 bedroom 3, U9, U10) will run cool in winter unless their dampers are reopened for the season, which is why the layout puts a seasonal marker on those four dampers. B: the zone panel gives each floor its own thermostat, and a lone-zone call runs at the blower minimum with bleed into the idle zone (section 9). C: each head is its own zone and modulates fan and compressor together, so there is nothing to balance between floors, only within them.

## 7. Design checklist D1 to D14

### Approach B

| # | Item | Result | Value | Note |
| --- | --- | --- | --- | --- |
| D1 | room loads at own peak and block at the house hour, diversity ratio at most 1.15 | PASS | sum of peaks 31,585 / block 28,993 = 1.09 |  |
| D2 | equipment sized to the block per Manual S (variable capacity 90 to 130 percent) | PASS | 3 ton nominal, about 31,000 to 33,000 Btuh at 103.8 F vs 29,793 total: 104 to 111 percent | expanded OEM data at 103.8 F and 27.9 F not read; heating at 27.9 F needs the OEM table (assumed) |
| D3 | room cfm table with own-peak and block-share columns printed at every outlet; documented airflows sum to the blower cfm | PASS | own-peak sum 1,308, blower 1,200; block-share column scales outlets by 0.92 |  |
| D4 | zoning test: floors zoned; C/H share ratio of every served room within 15 percent of its zone thermostat room | OPEN | outside 15 percent: M1 0.64, M6 0.83, U3 0.67, U4 0.85, U7 0.64, U9 0.80, U10 0.60 | exceptions named: entry (slab edge, heating heavy) and bedroom 3 (shaded south slider) are Manual J 11-21 exceptions; two zones by floor is the design |
| D5 | every zone design cfm at or above the blower low stage; no bypass; bleed specified | FAIL | main 650 vs low 804; upper 562 vs low 804; no bypass; 15 percent bleed | the 804 cfm is the two-stage default; with a communicating inverter the OEM sets a lower minimum (SS-GAVPTC note 1), not read; see section 9 |
| D6 | outlet selection per Manual T at design and low-stage cfm; face at most 700 fpm; register drop at most 0.03 | PASS | A618 sizes chosen for face velocity at or under 600 fpm; max 583 fpm, max Ps 0.021;  | throw data exist for 10x6 and 12x6 only; the 8x4 to 12x4 sizes need the catalogue rows read; T50 approximated as 1.5 x T75 |
| D7 | heating throw and stratification: supply at most 105 F at high outlets; heating cfm gives T75 at least 75 percent of cooling | OPEN | heat pump supply 95 to 105 F at the design airflow; heating cfm per room at 30 F rise is 0.78 of cooling cfm on average | winter deflection 15 deg down on the double-deflection grilles noted on the layout; OEM heating airflow table not read |
| D8 | returns: one ducted central return per floor at most 500 fpm face; master suite ducted return; every bedroom a transfer grille sized from RR-0005 | PASS | R-main 650 cfm, 250 sq in free; R-upper 434 cfm, 167 sq in free; R-master 128 cfm, 49 sq in free; transfer U7 53 sq in net, U9 47 sq in net |  |
| D9 | thermostats on interior walls, 5 ft, occupied rooms, out of every throw; remote sensors listed | PASS | main x3,y34.67; upper x2.5,y17; sensors in U2 and U7 |  |
| D10 | ducts inside the envelope; none over deck ceilings, porch or garage cavity unless the insulation line is drawn below; riser through the rated assembly 26 ga | OPEN | over the garage cavity: U7 2.0 ft; U10 19.3 ft; R-main 6.0 ft; R-upper 7.0 ft; R-master 16.0 ft; penetrations of the garage assembly: supply riser through the alcove ceiling (14x20, 26 ga); main return through the alcove north wall; upper return drop through the alcove ceiling | the bays over the garage need the IECC R403.3.2 item 3 section (R-19 under the duct, continuous air barrier) drawn before any duct goes there; U10's 4 in rigid run is the Rule 2 candidate to delete |
| D11 | balancing damper at every branch takeoff, accessible; design cfm labelled at every register | PASS | 15 takeoff dampers; cfm in the schedule at every outlet |  |
| D12 | static pressure budget: design external static within the blower table | PASS | design ESP 0.50 at 1,200 cfm against the SS-GAVPTC recommended 0.1 to 0.5; ASP 0.266 |  |
| D13 | ERV: 62.2 rate printed; dedicated bedroom supplies and bath exhausts, or the coupling stated | PASS | 102 cfm; dedicated 4 in supplies to U1, U2, U7, U9; exhausts from M2, U4 toilet room, U8 |  |
| D14 | solar first: rooms with peak/average glass gain over 1.5 listed with the Btuh saved before HVAC compensates | OPEN | flagged in the load run: M4, M6, U1, U2, U3, U4, U10; SHGC 0.23 cuts the block 1,566 Btuh (loads report section 11) | OPEN: a shading decision is Alan's, before the equipment is bought |

### Approach C

| # | Item | Result | Value | Note |
| --- | --- | --- | --- | --- |
| D1 | room loads at own peak and block at the house hour, diversity ratio at most 1.15 | PASS | sum of peaks 31,585 / block 28,993 = 1.09 |  |
| D2 | equipment sized to the zone blocks per Manual S | OPEN | main 18k nominal vs 15,710 (115 percent nominal); upper 15k nominal vs 13,587 (110 percent nominal); derated capacity at 103.8 F not read | OPEN: mid-static heads typically deliver 85 to 90 percent of nominal at 103.8 F, which puts the upper head near 95 percent of its zone peak |
| D3 | room cfm table printed at every outlet; documented airflows sum to the head cfm | PASS | own-peak sum 1,164 vs heads 1,080; head-share column scales by 0.94 (main) and 0.92 (upper) |  |
| D4 | zoning test: floors zoned; C/H share ratio of every served room within 15 percent of its zone thermostat room | OPEN | outside 15 percent: M1 0.64, M6 0.83, U3 0.67, U4 0.85, U7 0.64, U9 0.80, U10 0.60 | exceptions named: entry (slab edge, heating heavy) and bedroom 3 (shaded south slider) are Manual J 11-21 exceptions; two zones by floor is the design |
| D5 | zone airflow versus blower minimum | PASS | not applicable: one head per zone, each modulates on its own; low speed 424 cfm |  |
| D6 | outlet selection per Manual T at design and low-stage cfm; face at most 700 fpm; register drop at most 0.03 | PASS | A618 sizes chosen for face velocity at or under 600 fpm; max 571 fpm, max Ps 0.020;  | throw data exist for 10x6 and 12x6 only; the 8x4 to 12x4 sizes need the catalogue rows read; T50 approximated as 1.5 x T75 |
| D7 | heating throw and stratification: supply at most 105 F at high outlets; heating cfm gives T75 at least 75 percent of cooling | OPEN | heat pump supply 95 to 105 F at the design airflow; heating cfm per room at 30 F rise is 0.88 of cooling cfm on average | winter deflection 15 deg down on the double-deflection grilles noted on the layout; OEM heating airflow table not read |
| D8 | returns: one ducted central return per floor at most 500 fpm face; master suite ducted return; every bedroom a transfer grille sized from RR-0005 | PASS | R-main 540 cfm, 207 sq in free; R-upper 417 cfm, 160 sq in free; R-master 123 cfm, 47 sq in free; transfer U7 51 sq in net, U9 45 sq in net |  |
| D9 | thermostats on interior walls, 5 ft, occupied rooms, out of every throw; remote sensors listed | PASS | main x3,y34.67; upper x2.5,y17; sensors in U2 and U7 |  |
| D10 | ducts inside the envelope; none over deck ceilings, porch or garage cavity unless the insulation line is drawn below; riser through the rated assembly 26 ga | OPEN | over the garage cavity: U7 2.0 ft; U10 19.3 ft; R-main 2.5 ft; R-master 3.7 ft; penetrations of the garage assembly: main supply plenum through the alcove ceiling (10x16, 26 ga); main return through the alcove north wall | the bays over the garage need the IECC R403.3.2 item 3 section (R-19 under the duct, continuous air barrier) drawn before any duct goes there; U10's 4 in rigid run is the Rule 2 candidate to delete |
| D11 | balancing damper at every branch takeoff, accessible; design cfm labelled at every register | PASS | 15 takeoff dampers; cfm in the schedule at every outlet |  |
| D12 | static pressure budget: design external static within the head's selectable settings | PASS | 0.40 setting used (0.14 to 0.60 available); ASP 0.269 |  |
| D13 | ERV: 62.2 rate printed; dedicated bedroom supplies and bath exhausts, or the coupling stated | PASS | 102 cfm; dedicated 4 in supplies to U1, U2, U7, U9; exhausts from M2, U4 toilet room, U8 |  |
| D14 | solar first: rooms with peak/average glass gain over 1.5 listed with the Btuh saved before HVAC compensates | OPEN | flagged in the load run: M4, M6, U1, U2, U3, U4, U10; SHGC 0.23 cuts the block 1,566 Btuh (loads report section 11) | OPEN: a shading decision is Alan's, before the equipment is bought |

Commissioning items C1 to C12 from the placement report are the field half of the same list: C1 leakage at rough-in (bays over the garage tested even though the code exempts ducts inside), C2 and C3 fan airflow and external static against the D12 budget, C4 room-by-room airflow against the D3 table at high and low stage, C5 bedroom pressure against the D8 transfer grilles, C7 throw against D6, C8 zone controls against D5 (B only), C9 ERV against D13, C10 sensors against D9, C11 balancing report against D11, C12 the comfort proof.

## 8. B against C, side by side

|  | B | C |
| --- | --- | --- |
| Equipment | Goodman AVPTC37C14 multi-position variable-speed air handler (3 ton chassis, internal coil) with a 3 ton inverter heat pump | Mitsubishi PEAD-A18AA8 (main floor) and PEAD-A15AA8 (upper floor) mid-static ceiling-concealed ducted heads |
| Blower cfm | 1,200 high, 804 low (two-stage default), one blower | main 540 wet, upper 540 wet (600 dry; each 424 low) |
| Design delta T | 24.8 F | main 29.8 F, upper 25.8 F |
| Zone cfm | main 650, upper 562 | main 540, upper 540 |
| Available static | 0.266 | 0.269 |
| TEL | 420 ft (to U9; return R-master) | 440 ft (to U9; return R-master) |
| Friction rate | 0.063 (worksheet 0.063) | 0.061 (worksheet 0.061) |
| Main trunk entrance | 12x12 at 694 cfm, 694 fpm | 14x10 at 575 cfm, 591 fpm |
| Upper legs | 10x8 west, 12x8 east | 10x8 west, 12x8 east |
| Riser and plenum | 14x20 riser, riser box with two zone dampers in chase A cells 1 and 2 | 10x16 main plenum into chase A; upper soffit plenum with two drops |
| Runouts | 15, 5 to 8 in | 15, 5 to 8 in |
| Garage assembly penetrations | 3: supply riser through the alcove ceiling (14x20, 26 ga); main return through the alcove north wall; upper return drop through the alcove ceiling | 2: main supply plenum through the alcove ceiling (10x16, 26 ga); main return through the alcove north wall |
| Duct over the garage cavity | U7 2.0 ft; U10 19.3 ft; R-main 6.0 ft; R-upper 7.0 ft; R-master 16.0 ft | U7 2.0 ft; U10 19.3 ft; R-main 2.5 ft; R-master 3.7 ft |
| Parts count | runouts 15; trunk_segments 12; returns 3; fittings 67; dampers 17; registers 15; grilles 5; equipment 2; filters 1; condensate_drains 1 | runouts 15; trunk_segments 12; returns 3; fittings 69; dampers 15; registers 15; grilles 5; equipment 3; filters 2; condensate_drains 2 |
| Comfort at part load | one inverter compressor modulates to the house load (18 to 22 kBtuh most of the design day); the zone dampers split it by floor; a lone zone call is below the 804 cfm documented low stage (see D5 and section 9), so the bleed setting and the OEM minimum airflow decide how well the idle zone stays mixed; the balancer sets each zone for its own season | each floor has its own inverter; no damper logic; each head turns its fan down to 424 cfm and its compressor to a fraction of nominal, so at the 8 AM main-floor load (9,784 Btuh) the coil runs at about 23.7 F delta T with long cycles; the two floors never fight |
| Filters, drains, outdoor units | 1 filter cabinet (plus the master return), 1 drain, 1 outdoor unit | 2 filter cabinets, 2 drains, 1 multi-zone or 2 single outdoor units |
| Noise | air handler in the garage; trunk velocities under 700 fpm | main head in the garage; upper head in the laundry soffit at 41 dB(A) at the 0.40 setting, 8 ft from the master door |
| Needs to be finalised | OEM expanded data at 103.8 F and 27.9 F, zoning panel minimum-airflow rule, damper drop, truss chase drawings (A and C), access panels, register catalogue rows for the 4 in tall sizes | OEM expanded data at 103.8 F and 27.9 F for both heads (single-zone vs multi-zone outdoor unit changes it), soffit section in the laundry, condensate routes, register catalogue rows |

## 9. Recommendation

B, because the one blower in that class carries the block with margin (1,200 cfm high, 1,315 chassis maximum, delta T 24.8 F) while C's 18k main head has none: it must run at its top wet-coil speed (540 cfm) at a 29.8 F coil delta T on the design afternoon, and a mid-static head derated to 103.8 F is at or under the main zone's 15,710 Btuh peak. Both approaches size the same 15 outlets and the same two returns to within one duct size and both land at the bottom of the friction-rate wedge (B 0.063, C 0.061), so the ducts do not decide it; B also keeps one outdoor unit, one filter cabinet, one drain and Alan's single metal core, at the price of one more garage penetration (the upper return drop) and the zone dampers.

B's open item is the zone minimum. The zone cfm (main 650, upper 562) are both under the 804 cfm documented low stage, so a lone upper call at 804 cfm would bleed 30 percent into the main zone, above the 10 to 20 percent Bailes rule. SS-GAVPTC note 1 says a communicating outdoor unit sets the airflow itself, and inverter systems in this class run the blower down with compressor capacity, so the real minimum is lower and undocumented here; the zoning control's minimum-airflow rule and the OEM's low-capacity airflow are the two numbers to get before B is final. If they do not come in under about 662 cfm, the fallback inside B is to let the dampers bleed 20 percent and accept a slightly warm idle zone, not a bypass. Checks failing: B 2, C 0 (checks.md). If the plans' mini-split note wins, C is sound with a 24k main head (742 cfm high) instead of the 18k, and two single-zone outdoor units rather than one multi-zone so each head keeps its turndown.

## 10. Assumptions register

| Term | Value | Source | Status |
| --- | --- | --- | --- |
| altitude factor | 0.903 | loads-v1 design-conditions.md, standard atmosphere at 2,800 ft | derived |
| design delta T | 20 F reference; B 24.8 F; C main 29.8 F, upper 25.8 F | brief: 20 F unless the equipment table says otherwise; derived from the blower table and the head airflow | derived |
| Btuh per cfm | 19.50 | 1.08 x 0.903 x 20 | derived |
| room cfm basis | room cooling sensible at its own peak hour | decisions.md (Alan) | sourced |
| zone cfm basis | zone cooling sensible at the zone's peak hour from loads.py hourly room loads | decisions.md; Manual Zr as summarised in the research note | derived |
| B blower cfm | 1,200 high / 804 low | Goodman SS-GAVPTC airflow data, 3 ton setting | sourced, representative |
| B design external static | 0.50 | SS-GAVPTC note 3: 0.1 to 0.5 recommended | sourced |
| B coil drop | 0 (inside the cabinet rating); CAPT3743C4 0.143 wet at 1,200 cfm for comparison | SS-GAVPTC; SS-GCoil | sourced |
| C heads | PEAD-A18AA8 main, PEAD-A15AA8 upper, 424/512/600 cfm, ESP 0.14 to 0.60 | Mitsubishi HWE2109A service manual | sourced, representative |
| C design external static | 0.40 | 0.40 setting; 0.60 available at plus 3 dB(A) | sourced |
| media filter drop | 0.11 at 1,200 cfm (B); 0.04 at 600 cfm (C) | Aprilaire 210 catalogue table; 600 cfm point via hvac-talk quotation of the Aprilaire curve | sourced / secondary |
| register drop | 0.031 at 700 fpm face | Hart & Cooley A618 engineering data | sourced |
| return grille and balancing damper drop | 0.03 each | Manual D default, MD3 copy section 6-5 | licensed-unverified |
| zone damper drop | 0.033 wide open | Honeywell ARD submittal, 0.0329 at 800 fpm | sourced |
| friction rate wedge | 0.06 to 0.18 | ACCA blog on the 2014 Manual D revision; hvacrschool.com | sourced |
| velocity limits | trunk 900, branch 700, return 700, register face 700, grille 500, filter grille 300 fpm | MD3 copy Table A1-1; brief | licensed-unverified / brief |
| fitting equivalent lengths | ASHRAE loss coefficients at 900/0.08 supply, 700/0.08 return | ASHRAE Principles of HVAC 9th ed. supplement (public); normalisation per Butler | sourced |
| Appendix 3 comparators | 1L 40, 2B 45, 4J 30, 4G 80, 5I 30, 6H 15, 8D 65, four-piece elbow 20, 12 8 ft | MD3 copy via the research note | licensed-unverified |
| flex roughness | 0.003 ft (RF 1.76 cross-check) | ASHRAE Fundamentals; MD3 copy Table A1-3 | sourced / licensed-unverified |
| galvanized roughness | 0.0003 ft | ASHRAE Fundamentals | sourced |
| truss layout | 24 in o.c. spanning east-west with a truss on the garage line y25.83 | A8, A9; the origin is assumed | assumed |
| truss chase | chase A x13 to 15, 24 in by clear depth, y23.83 to 46; chase C x9.5 to 11.5 (B) | Alan: typical size where the routing wants it | assumed |
| duct height in the cavity | 14 in in a chase, 10 in in a bay, 8 in round crossing at a flat section | 16 in clear depth | derived |
| garage footprint | x9 to 32, y2 to 22.83 plus alcove x9 to 20.5, y22.83 to 25.83 | rooms.csv M7 | sourced |
| outlet locations | placement report section 4 with five moves | research/ducts/placement-and-comfort-fable.md | sourced / derived |
| A618 register data | Ak, Ps, throw to 75 fpm | hartandcooley.com/uploads/a618_621.pdf | sourced |
| T50 from T75 | 1.5 x | 1/x decay in the fully developed jet, ASHRAE Fundamentals ch. 20 | assumed |
| transfer grille sizing | Q = 1.07 A dP^0.5 at 3 Pa, 75 percent free area | BSC RR-0005 | sourced |
| ERV rate | 102 cfm | loads-v1 results.json air.cfm_vent (ASHRAE 62.2) | sourced |
| Manual S capacity at 103.8 F | 3 ton about 31 to 33 kBtuh; mid-static heads 85 to 90 percent of nominal | research note section 1; OEM expanded data not read | assumed |
| bleed to the idle zone (B) | 15 percent | Energy Vanguard zoning article, 10 to 20 percent | sourced |