# Layout B, Lot 308

Duct routing following the ACCA Manual D procedure. Representative equipment, not a selected model. This software is not ACCA-approved. First-pass design for review by a qualified designer.

Coordinates are feet, x east of grid 1, y north of grid A, the frame of rooms.csv. Floor trusses are 1 ft 7-1/4 in deep at 24 in o.c., spanning east-west; bay k runs from y = 25.83 + 2k to 25.83 + 2(k+1) (a truss is assumed on the garage line y25.83; the truss designer sets the real layout). Clear depth between chords about 16 in; ducts are held to 14 in tall in the chase and 10 in tall in a bay. Anything crossing a truss passes through the web openings or an engineered chase.

## Equipment and chases

- Air handler: Goodman AVPTC37C14 multi-position variable-speed air handler (3 ton chassis, internal coil) with a 3 ton inverter heat pump, upflow, in the garage mechanical alcove (A3: x9 to 20.5, y22.83 to 25.83) at x10 to 13, y23 to 25, on the 18 in platform. Return enters the bottom through a 4 in media filter cabinet; supply leaves the top through a 14x20 riser, 26 ga, sealed, R-8, up through the rated alcove ceiling (5/8 in Type X) into chase A.

- Chase A: engineered truss chase x13 to 15 (24 in wide) by the clear truss depth, from the alcove cell (y23.83 to 25.83) north to y46. The riser box sits in the first two cells (y23.83 to 27.83); the main-floor trunk runs north from y27.83. Chase A's first cell is over the alcove: R-19 batts against the gyp below the duct, air barrier continuous, per IECC R403.3.2 item 3.
- Zone dampers: two motorised dampers in the riser box, one on the main trunk collar (north face) and one on the upper-floor collar (feeding both legs east and west). No bypass. Bleed 15 percent to the idle zone. The riser box is in the truss cavity, accessible from a 24x24 ceiling access panel in the alcove ceiling (garage side, 26 ga box, gasketed).
- Chase C: return chase x9.5 to 11.5, from bay y21.83 to 23.83 down through the alcove ceiling at y22.9 to 23.8 to the filter cabinet (26 ga, R-8 in the alcove).

## Supply trunks

| Segment | Where | Length ft | cfm | Size in | fpm |  |
| --- | --- | --- | --- | --- | --- | --- |
| main-1 | x14.0, y27.8 to y28.5 | 0.7 | 694 | 12x12 | 694 |  |
| main-2 | x14.0, y28.5 to y36.8 | 8.3 | 559 | 12x12 | 559 |  |
| main-3 | x14.0, y36.8 to y38.8 | 2.0 | 482 | 12x12 | 482 |  |
| main-4 | x14.0, y38.8 to y40.8 | 2.0 | 375 | 12x12 | 375 |  |
| main-5 | x14.0, y40.8 to y44.8 | 4.5 | 254 | 12x6 | 508 | reduce |
| upper_w-1 | bay y25.8 to 27.8, x13.0 to x11.0 | 2.0 | 285 | 10x8 | 513 |  |
| upper_w-2 | bay y25.8 to 27.8, x11.0 to x10.0 | 1.0 | 253 | 10x8 | 455 |  |
| upper_w-3 | bay y25.8 to 27.8, x10.0 to x5.0 | 5.5 | 88 | 6x6 | 352 | reduce |
| upper_e-1 | bay y25.8 to 27.8, x15.0 to x21.0 | 6.0 | 329 | 12x8 | 494 |  |
| upper_e-2 | bay y25.8 to 27.8, x21.0 to x25.0 | 4.0 | 201 | 12x8 | 302 |  |
| upper_e-3 | bay y25.8 to 27.8, x25.0 to x28.0 | 3.0 | 102 | 6x6 | 408 | reduce |
| upper_e-4 | bay y25.8 to 27.8, x28.0 to x29.5 | 2.0 | 46 | 6x6 | 184 |  |

Takeoffs are 45 deg entry taps with a balancing damper at the trunk, accessible from the ceiling below (main-floor ceiling registers) or from a 12x12 access panel next to the tap (upper legs). The trunk extends 6 in past the last takeoff before the end cap; no takeoff in an end cap (RSES rule).

## Supply runouts

| Run | Room | cfm | Duct | Tap (x, y) | Register (x, y) | Outlet | Span ft | Webs crossed | Over garage ft | A618 size | Note |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1a | M1+M2+M3 | 83 | 7 in flex | (14.0, 28.5) | (7.0, 31.0) | ceiling | 9.5 | 1 |  | 8x4 | hall ceiling, 2-way, blowing south; placement report put the M1 outlet at x4,y12, split here into hall and entry |
| M1b | M1 | 52 | 5 in rigid | (14.0, 28.5) | (4.0, 12.0) | ceiling | 26.5 | 8 |  | 8x4 | entry ceiling at x4,y12 (placement report); round galvanized west in bay y27.83 to 29.83 then south along x4 through the truss webs, under the upper west leg's end cap |
| M4A | M4 | 121 | 8 in flex | (14.0, 40.8) | (4.0, 40.5) | ceiling | 10.3 | 0 |  | 12x4 | under the loft, long throw north along the west glass; y40.5 not y38 so the flex does not cross the U1b runout |
| M4B | M4 | 77 | 7 in flex | (14.0, 36.8) | (11.0, 36.0) | ceiling | 3.8 | 0 |  | 8x4 | toward the island end |
| M5W | M5 | 127 | 8 in flex | (14.0, 44.8) | (16.5, 45.5) | ceiling | 3.2 | 0 |  | 12x4 | in the 3 ft inside ceiling strip y43.83 to 47, throwing north |
| M5E | M5 | 127 | 8 in flex | (14.0, 44.8) | (26.0, 45.0) | ceiling | 12.2 | 0 |  | 12x4 | east in bay y43.83 to 45.83, throwing north |
| M6 | M6 | 107 | 7 in flex | (14.0, 38.8) | (24.0, 38.0) | ceiling | 10.8 | 0 |  | 10x4 | 2-way east and north, away from the hood at x31,y31 |
| U1a | U1+U5+U6+U8 | 91 | 7 in flex | (10.0, 26.8) | (9.5, 27.0) | sidewall | 0.7 + 8 stack | 0 |  | 8x4 | loft east wall (laundry partition), 8 ft high, blowing west |
| U1b | U1 | 74 | 6 in flex | (10.0, 26.8) | (9.5, 38.0) | sidewall | 11.7 + 8 stack | 5 |  | 8x4 | loft east wall (master partition), 8 ft high, blowing west; flex north through the truss webs over the living room |
| U2 | U2 | 128 | 8 in flex | (21.0, 26.8) | (21.0, 33.0) | sidewall | 6.2 + 8 stack | 3 |  | 12x4 | south wall (master bath partition), 8 ft high, blowing north 14 ft; x21 keeps clear of the master return drop |
| U3 | U3 | 46 | 5 in flex | (29.5, 26.8) | (30.0, 38.0) | floor | 11.7 | 5 |  | 8x4 | 4x10 floor register near the east transom; y38 keeps the flex under 15 ft |
| U4 | U4 | 56 | 6 in flex | (28.0, 26.8) | (28.0, 29.0) | floor | 2.2 | 1 |  | 8x4 | 4x10 floor register outside the wet zone, over the kitchen |
| U7 | U7 | 99 | 7 in flex | (25.0, 26.8) | (25.0, 20.83) | sidewall | 6.0 + 8 stack | 3 | 2.0 | 10x4 | north wall (bath partition), blowing south 15 ft; the last bays are over the garage |
| U9 | U9 | 88 | 7 in flex | (5.0, 26.8) | (3.5, 17.0) | sidewall | 11.3 + 8 stack | 4 |  | 8x4 | north wall (loft partition), blowing south; over the entry, inside |
| U10 | U10 | 32 | 5 in rigid | (11.0, 26.8) | (11.0, 6.5) | floor | 20.3 | 10 | 19.3 | 8x4 | 4x10 floor register; round galvanized south through the truss webs over the garage (IECC R403.3.2 item 3 bays); Rule 2 candidate for deletion, the door-open alternative is no outlet |

Flex standard of care on the drawing: cut to length, 0 to 4 percent compression, straight centreline, sag under 0.5 in per ft, supports at 4 ft or less on 1.5 in straps, bend radius one diameter or more, a rigid elbow at the boot where the turn is tight (Manual D section 4-3 as read in the MD3 copy; ADC standard). A run that misses this is re-rated with Appendix 16 multipliers, and the U1b, U3, U9 runs (11 to 12 ft) are the ones that pay for it first.

## Returns

| Return | Serves | cfm | Duct | Grille | Grille area | Over garage ft | Note |
| --- | --- | --- | --- | --- | --- | --- | --- |
| R-main | main zone | 650 | 14x10 | 30x10 sidewall grille on the alcove north wall (y25.83), living-room side, x10 to 12.5, top at 9 ft | 250 sq in free (75 percent grille, 500 fpm face) | 6.0 | 26 ga, sealed, R-8 inside the alcove |
| R-upper | upper zone | 434 | 14x8 | 30x8 high wall grille, loft east wall (x9.5), y21 to 23.5, top at 9 ft | 167 sq in free (75 percent grille, 500 fpm face) | 7.0 | the master return joins in bay y21.83 to 23.83; 26 ga and R-8 from the alcove ceiling down |
| R-master | U2 | 128 | 7 in round | 14x8 high sidewall grille, master south wall (y33) at x22, top at 9 ft | 49 sq in free (75 percent grille, 500 fpm face) | 16.0 | the one crossing in B: a 5x16 flat section passes over the 8 in tall east leg (13 in of the 16 in clear depth) |

Transfer grilles over the bedroom doors, BSC RR-0005 at 3 Pa (Q = 1.07 A dP^0.5):

| Bedroom | To | cfm | Net free sq in | Gross at 75 percent | Grille |
| --- | --- | --- | --- | --- | --- |
| U7 | hall | 99 | 53 | 71 | 12x8 at 75 percent (72 sq in net) |
| U9 | loft | 88 | 47 | 63 | 12x8 at 75 percent (72 sq in net) |

Seasonal damper marks: M1a, M1b, U7, U9, U10 dampers carry a summer and a winter position (heating share high relative to cooling).

Door undercuts only for the powder, broom closet, master WIC and bath, laundry, hall bath and WIC 2 (all under 60 cfm or served by an adjacent room).

## Thermostats and sensors

Main: broom-closet wall facing the living room, x3, y34.67, 5 ft high. Upper: loft south wall, x2.5, y17, 5 ft high. Remote sensors in the master bedroom (night) and bedroom 3. Neither thermostat wall carries an outlet.

## ERV

ASHRAE 62.2 rate from the load run: 102 cfm. Dedicated ERV ducts: fresh air to the master bedroom, bedroom 2, bedroom 3 and the loft (4 in flex from the ERV in the alcove or laundry soffit), exhaust from the powder, master toilet room and hall bath. The ERV runs independently of the blowers, so no interlock is needed; if the mechanical contractor couples it to the return instead, tie the supply into the return plenum downstream of the filter with the blower interlocked to the ERV (plan note 5).

## Plan sketch, main floor (1 ft per column, 2 ft per row; | and = trunk, + tap, S register, R return grille, : and . garage lines)

```
55 |                               |
53 |                               |
51 |                               |
49 |                               |
47 |               S               |
45 |             +           S     |
43 |             |                 |
41 |   S         +                 |
39 |             +         S       |
37 |          S  +                 |
35 |             |                 |
33 |      S      |                 |
31 |             |                 |
29 |             +                 |
27 |        .R..........           |
25 |                               |
23 |        ........................
21 |        :                      |
19 |        :                      |
17 |        :                      |
15 |        :                      |
13 |   S    :                      |
11 |        :                      |
 9 |        :                      |
 7 |        :                      |
 5 |        :                      |
 3 |--------:----------------------|
 1                                  
   012345678901234567890123456789012
```

## Plan sketch, upper floor (1 ft per column, 2 ft per row; | and = trunk, + tap, S register, R return grille, : and . garage lines)

```
55 |                               |
53 |                               |
51 |                               |
49 |                               |
47 |                               |
45 |                               |
43 |                               |
41 |                               |
39 |         S                   S |
37 |                               |
35 |                               |
33 |                    SR         |
31 |                               |
29 |         S                 S   |
27 |    +====++==.======+===+==+=+ |
25 |                               |
23 |        ........................
21 |        :R              S      |
19 |        :                      |
17 |   S    :                      |
15 |        :                      |
13 |        :                      |
11 |        :                      |
 9 |        :                      |
 7 |        : S                    |
 5 |        :                      |
 3 |--------:----------------------|
 1                                  
   012345678901234567890123456789012
```