# Layout C, Lot 308

Duct routing following the ACCA Manual D procedure. Representative equipment, not a selected model. This software is not ACCA-approved. First-pass design for review by a qualified designer.

Coordinates are feet, x east of grid 1, y north of grid A, the frame of rooms.csv. Floor trusses are 1 ft 7-1/4 in deep at 24 in o.c., spanning east-west; bay k runs from y = 25.83 + 2k to 25.83 + 2(k+1) (a truss is assumed on the garage line y25.83; the truss designer sets the real layout). Clear depth between chords about 16 in; ducts are held to 14 in tall in the chase and 10 in tall in a bay. Anything crossing a truss passes through the web openings or an engineered chase.

## Equipment and chases

- Main-floor head: PEAD-A18AA8, hung under the alcove ceiling at x16 to 19, y23 to 25.5 (unit 35-7/16 x 28-7/8 x 9-7/8 in), inlet facing east through a 4 in filter cabinet fed by the kitchen-side return grille, outlet facing west into a 10x16 plenum that turns up through the rated alcove ceiling into chase A (26 ga, sealed, R-8 in the alcove). Condensate: built-in lift, drain to the softener drain.

- Upper-floor head: PEAD-A15AA8 in a 14 in deep soffit along the laundry south wall (x9.5 to 17, y23.17 to 25.6, soffit bottom at 8 ft 8 in), unit at x10 to 13, inlet facing west through a filter cabinet behind the loft-wall return grille, outlet facing east into a soffit plenum that feeds two drops through the laundry floor into bay y25.83 to 27.83, one each side of chase A (west drop x11.5 to 13, east drop x15.2 to 17). The soffit is inside the envelope; nothing on the upper system touches the garage assembly. Service: 24x24 panel in the soffit face. Condensate: to the laundry standpipe.

- Chase A: engineered truss chase x13 to 15 by the clear truss depth, from the alcove cell (y23.83 to 25.83) north to y46; main-floor trunk from y27.83 north. First cell gets the IECC item 3 treatment.

## Supply trunks

| Segment | Where | Length ft | cfm | Size in | fpm |  |
| --- | --- | --- | --- | --- | --- | --- |
| main-1 | x14.0, y27.8 to y28.5 | 0.7 | 575 | 14x10 | 591 |  |
| main-2 | x14.0, y28.5 to y36.8 | 8.3 | 463 | 14x10 | 476 |  |
| main-3 | x14.0, y36.8 to y38.8 | 2.0 | 399 | 14x10 | 410 |  |
| main-4 | x14.0, y38.8 to y40.8 | 2.0 | 310 | 14x10 | 319 |  |
| main-5 | x14.0, y40.8 to y44.8 | 4.5 | 210 | 8x8 | 472 | reduce |
| upper_w-1 | bay y25.8 to 27.8, x11.5 to x11.0 | 0.5 | 274 | 10x8 | 493 |  |
| upper_w-2 | bay y25.8 to 27.8, x11.0 to x10.0 | 1.0 | 243 | 10x8 | 437 |  |
| upper_w-3 | bay y25.8 to 27.8, x10.0 to x5.0 | 5.5 | 84 | 6x6 | 336 | reduce |
| upper_e-1 | bay y25.8 to 27.8, x17.0 to x21.0 | 4.0 | 315 | 12x8 | 472 |  |
| upper_e-2 | bay y25.8 to 27.8, x21.0 to x25.0 | 4.0 | 192 | 12x8 | 288 |  |
| upper_e-3 | bay y25.8 to 27.8, x25.0 to x28.0 | 3.0 | 97 | 6x6 | 388 | reduce |
| upper_e-4 | bay y25.8 to 27.8, x28.0 to x29.5 | 2.0 | 44 | 6x6 | 176 |  |

Takeoffs are 45 deg entry taps with a balancing damper at the trunk, accessible from the ceiling below (main-floor ceiling registers) or from a 12x12 access panel next to the tap (upper legs). The trunk extends 6 in past the last takeoff before the end cap; no takeoff in an end cap (RSES rule).

## Supply runouts

| Run | Room | cfm | Duct | Tap (x, y) | Register (x, y) | Outlet | Span ft | Webs crossed | Over garage ft | A618 size | Note |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| M1a | M1+M2+M3 | 69 | 6 in flex | (14.0, 28.5) | (7.0, 31.0) | ceiling | 9.5 | 1 |  | 8x4 | hall ceiling, 2-way, blowing south; placement report put the M1 outlet at x4,y12, split here into hall and entry |
| M1b | M1 | 43 | 5 in rigid | (14.0, 28.5) | (4.0, 12.0) | ceiling | 26.5 | 8 |  | 8x4 | entry ceiling at x4,y12 (placement report); round galvanized west in bay y27.83 to 29.83 then south along x4 through the truss webs, under the upper west leg's end cap |
| M4A | M4 | 100 | 7 in flex | (14.0, 40.8) | (4.0, 40.5) | ceiling | 10.3 | 0 |  | 10x4 | under the loft, long throw north along the west glass; y40.5 not y38 so the flex does not cross the U1b runout |
| M4B | M4 | 64 | 6 in flex | (14.0, 36.8) | (11.0, 36.0) | ceiling | 3.8 | 0 |  | 8x4 | toward the island end |
| M5W | M5 | 105 | 7 in flex | (14.0, 44.8) | (16.5, 45.5) | ceiling | 3.2 | 0 |  | 10x4 | in the 3 ft inside ceiling strip y43.83 to 47, throwing north |
| M5E | M5 | 105 | 7 in flex | (14.0, 44.8) | (26.0, 45.0) | ceiling | 12.2 | 0 |  | 10x4 | east in bay y43.83 to 45.83, throwing north |
| M6 | M6 | 89 | 7 in flex | (14.0, 38.8) | (24.0, 38.0) | ceiling | 10.8 | 0 |  | 8x4 | 2-way east and north, away from the hood at x31,y31 |
| U1a | U1+U5+U6+U8 | 88 | 7 in flex | (10.0, 26.8) | (9.5, 27.0) | sidewall | 0.7 + 8 stack | 0 |  | 8x4 | loft east wall (laundry partition), 8 ft high, blowing west |
| U1b | U1 | 71 | 6 in flex | (10.0, 26.8) | (9.5, 38.0) | sidewall | 11.7 + 8 stack | 5 |  | 8x4 | loft east wall (master partition), 8 ft high, blowing west; flex north through the truss webs over the living room |
| U2 | U2 | 123 | 8 in flex | (21.0, 26.8) | (21.0, 33.0) | sidewall | 6.2 + 8 stack | 3 |  | 12x4 | south wall (master bath partition), 8 ft high, blowing north 14 ft; x21 keeps clear of the master return drop |
| U3 | U3 | 44 | 5 in flex | (29.5, 26.8) | (30.0, 38.0) | floor | 11.7 | 5 |  | 8x4 | 4x10 floor register near the east transom; y38 keeps the flex under 15 ft |
| U4 | U4 | 53 | 6 in flex | (28.0, 26.8) | (28.0, 29.0) | floor | 2.2 | 1 |  | 8x4 | 4x10 floor register outside the wet zone, over the kitchen |
| U7 | U7 | 95 | 7 in flex | (25.0, 26.8) | (25.0, 20.83) | sidewall | 6.0 + 8 stack | 3 | 2.0 | 10x4 | north wall (bath partition), blowing south 15 ft; the last bays are over the garage |
| U9 | U9 | 84 | 7 in flex | (5.0, 26.8) | (3.5, 17.0) | sidewall | 11.3 + 8 stack | 4 |  | 8x4 | north wall (loft partition), blowing south; over the entry, inside |
| U10 | U10 | 31 | 5 in rigid | (11.0, 26.8) | (11.0, 6.5) | floor | 20.3 | 10 | 19.3 | 8x4 | 4x10 floor register; round galvanized south through the truss webs over the garage (IECC R403.3.2 item 3 bays); Rule 2 candidate for deletion, the door-open alternative is no outlet |

Flex standard of care on the drawing: cut to length, 0 to 4 percent compression, straight centreline, sag under 0.5 in per ft, supports at 4 ft or less on 1.5 in straps, bend radius one diameter or more, a rigid elbow at the boot where the turn is tight (Manual D section 4-3 as read in the MD3 copy; ADC standard). A run that misses this is re-rated with Appendix 16 multipliers, and the U1b, U3, U9 runs (11 to 12 ft) are the ones that pay for it first.

## Returns

| Return | Serves | cfm | Duct | Grille | Grille area | Over garage ft | Note |
| --- | --- | --- | --- | --- | --- | --- | --- |
| R-main | main zone | 540 | 16x8 | 30x10 sidewall grille on the alcove north wall (y25.83), kitchen side, x17.5 to 20, top at 9 ft | 207 sq in free (75 percent grille, 500 fpm face) | 2.5 | the head hangs under the alcove ceiling at x16 to 19; nothing opens to the garage |
| R-upper | upper zone | 417 | 10x10 | 30x10 wall grille through the loft east wall (x9.5) at y23.5 to 26, top at 9 ft, straight into the soffit return box | 160 sq in free (75 percent grille, 500 fpm face) |  | the head sits in a soffit along the laundry south wall, inlet facing south, outlet facing north |
| R-master | U2 | 123 | 7 in round | 14x8 high sidewall grille, master south wall (y33) at x22, top at 9 ft | 47 sq in free (75 percent grille, 500 fpm face) | 3.7 | the one crossing in C, same flat section as B; 3.7 ft of the run is in the bay over the alcove and gets R-8 and the item 3 treatment |

Transfer grilles over the bedroom doors, BSC RR-0005 at 3 Pa (Q = 1.07 A dP^0.5):

| Bedroom | To | cfm | Net free sq in | Gross at 75 percent | Grille |
| --- | --- | --- | --- | --- | --- |
| U7 | hall | 95 | 51 | 68 | 12x8 at 75 percent (72 sq in net) |
| U9 | loft | 84 | 45 | 60 | 12x8 at 75 percent (72 sq in net) |

Seasonal damper marks: M1a, M1b, U7, U9, U10 dampers carry a summer and a winter position (heating share high relative to cooling).

Door undercuts only for the powder, broom closet, master WIC and bath, laundry, hall bath and WIC 2 (all under 60 cfm or served by an adjacent room).

## Thermostats and sensors

Main: broom-closet wall facing the living room, x3, y34.67, 5 ft high. Upper: loft south wall, x2.5, y17, 5 ft high. Remote sensors in the master bedroom (night) and bedroom 3. Neither thermostat wall carries an outlet.

## ERV

ASHRAE 62.2 rate from the load run: 102 cfm. Dedicated ERV ducts: fresh air to the master bedroom, bedroom 2, bedroom 3 and the loft (4 in flex from the ERV in the alcove or laundry soffit), exhaust from the powder, master toilet room and hall bath. The ERV runs independently of the blowers, so no interlock is needed; if the mechanical contractor couples it to the return instead, tie the supply into the return plenum downstream of the filter with the blower interlocked to the ERV (plan note 5).

## Plan sketch, main floor (1 ft per column, 2 ft per row; | and = trunk, + tap, S register, R return grille, : and . garage lines)

```
55 |                               |
53 |                               |
51 |                               |
49 |                               |
47 |               S               |
45 |             +           S     |
43 |             |                 |
41 |   S         +                 |
39 |             +         S       |
37 |          S  +                 |
35 |             |                 |
33 |      S      |                 |
31 |             |                 |
29 |             +                 |
27 |        .........R..           |
25 |                               |
23 |        ........................
21 |        :                      |
19 |        :                      |
17 |        :                      |
15 |        :                      |
13 |   S    :                      |
11 |        :                      |
 9 |        :                      |
 7 |        :                      |
 5 |        :                      |
 3 |--------:----------------------|
 1                                  
   012345678901234567890123456789012
```

## Plan sketch, upper floor (1 ft per column, 2 ft per row; | and = trunk, + tap, S register, R return grille, : and . garage lines)

```
55 |                               |
53 |                               |
51 |                               |
49 |                               |
47 |                               |
45 |                               |
43 |                               |
41 |                               |
39 |         S                   S |
37 |                               |
35 |                               |
33 |                    SR         |
31 |                               |
29 |         S                 S   |
27 |    +====++=....====+===+==+=+ |
25 |         R                     |
23 |        ........................
21 |        :               S      |
19 |        :                      |
17 |   S    :                      |
15 |        :                      |
13 |        :                      |
11 |        :                      |
 9 |        :                      |
 7 |        : S                    |
 5 |        :                      |
 3 |--------:----------------------|
 1                                  
   012345678901234567890123456789012
```